Round Flow

SkyAir Ceiling Mounted Cassette Round Flow (FCFC)

SkyAir Inverter

Energy-saving round flow ceiling Cassette AC with a cleanliness sensor and smart temperature control.
Technology
Inverter
SkyAir Ceiling Mounted Cassette Round Flow (FCFC)

Key Features

ENERGY SAVING

ENERGY SAVING

Using Inverter technology and R32, power consumption is reduced by up to 35% based on average CSPF* value *CSPF = Cooling Seasonal Performance Factor

360° AIRFLOW

360° AIRFLOW

DAIKIN Sky Air is designed to deliver cool airflow to every part of the room where it is installed, backed by powerful cooling distributed evenly to every corner

EASY MAINTENANCE

EASY MAINTENANCE

Without having to remove many parts of the unit, the DAIKIN SkyAir Ceilling Mounted Cassette Round Flow is easy to maintain. The drain outlet used to check the drain pan and drain water is located at one corner of the front panel and can be seen after opening the AC grille

Other Features

Weekly Timer Mode

The AC ON/OFF mode and temperature can be set for each day of the week, so it can be tailored to your needs

Auto-On Mode

Works when power returns after an outage. This feature remembers settings such as cooling type, airflow, temperature and more

Self-Diagnosis

Detects malfunctions according to the codes shown on the remote. Makes it quick and easy to take action

Technical Specifications

ParameterFCFC40DVM4 (1 Phase)FCFC50DVM4 (1 Phase)FCFC60DVM4 (1 Phase)FCFC71DVM4 (1 Phase)FCFC85DVM4 (1 Phase)FCFC100DVM4 (1 Phase)FCFC71DVM4 (3 Phase)FCFC85DVM4 (3 Phase)FCFC100DVM4 (3 Phase)FCF1251DVM4 (3 Phase)FCFC140DVM4 (3 Phase)
Model Name · Indoor Unit FCFC40DVM4FCFC50DVM4FCFC60DVM4FCFC71DVM4FCFC85DVM4FCFC100DVM4FCFC71DVM4FCFC85DVM4FCFC100DVM4FCFC125DVM4FCFC140DVM4
Model Name · Outdoor Unit RZFC40DVM4RZFC50DVM4RZFC60DVM4RZFC71DVM4RZFC85DVM4RZFC100DVM4RZFC71DVM4RZFC85DVM4RZFC100DVM4RZFC125DVM4RZFC140DVM4
Power Supply · Outdoor Unit 1 Phase, 220-240 / 220-230, 50 / 60Hz1 Phase, 220-240 / 220-230, 50 / 60Hz1 Phase, 220-240 / 220-230, 50 / 60Hz1 Phase, 220-240 / 220-230, 50 / 60Hz1 Phase, 220-240 / 220-230, 50 / 60Hz1 Phase, 220-240 / 220-230, 50 / 60Hz3 Phase, 380-415V, 50Hz3 Phase, 380-415V, 50Hz3 Phase, 380-415V, 50Hz3 Phase, 380-415V, 50Hz3 Phase, 380-415V, 50Hz
Cooling Capacity (Min. - Max.) KW4.0 (1.8-4.5)5.0 (2.3-5.6)6.0 (2.6-6.3)7.1 (3.2-8.0)8.5 (4.2-10.0)10.0 (5.0-11.2)7.1 (3.2-8.0)8.5 (4.2-10.0)10.0 (5.0-11.2)12.5 (5.7-14.0)14.0 (6.2-15.5)
Cooling Capacity (Min. - Max.) Btu/h13,600 (6,100-15,400)17,100 (7,800-19,100)20,500 (8,900-21,500)24,200 (10,900-27,300)29,000 (14,300-34,100)34,100 (17,100-38,200)24,200 (10,900-27,300)29,000 (14,300-34,100)34,100 (17,100-38,200)42,700 (19,500-47,800)47,800 (21,200-52,900)
Power Consumption · Cooling Kw1.261.571.892.382.853.352.382.853.354.705.88
COP Kw/Kw3.183.183.182.982.982.982.982.982.982.662.38
CSPF Kwh/Kwh5.134.904.904.674.674.674.674.674.674.294.10
Indoor Unit · Color · Unit WhiteWhiteWhiteWhiteWhiteWhiteWhiteWhiteWhiteWhiteWhite
Indoor Unit · Color · Decorative Panel Fresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh WhiteFresh White
Indoor Unit · Airflow Rate (H / M / L) m3/min19 / 14 / 1119 / 14 / 1119 / 14 / 1123 / 18 / 1323 / 18 / 1334 / 27 / 2023 / 18 / 1323 / 18 / 1334 / 27 / 2036 / 29 / 2136 / 29 / 21
Indoor Unit · Airflow Rate (H / M / L) cfm671 / 494 / 388671 / 494 / 388671 / 494 / 388812 / 635 / 459812 / 635 / 4591,200 / 953 / 706812 / 635 / 459812 / 635 / 4591,200 / 953 / 7061,271 / 1,024 / 7411,271 / 1,024 / 741
Indoor Unit · Sound Pressure Level (H / M / L) Db(A)37 / 32 / 2837 / 32 / 2837 / 32 / 2837 / 34 / 2838 / 34 / 2945 / 38 / 3337 / 32 / 2837 / 32 / 2837 / 32 / 2837 / 34 / 2838 / 34 / 29
Indoor Unit · Dimensions (HxWxD) · Unit mm256 x 840 x 840256 x 840 x 840256 x 840 x 840256 x 840 x 840256 x 840 x 840298 x 840 x 840256 x 840 x 840256 x 840 x 840298 x 840 x 840298 x 840 x 840298 x 840 x 840
Indoor Unit · Dimensions (HxWxD) · Decorative Panel mm50 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 95050 x 950 x 950
Indoor Unit · Net Weight · Unit kg1919192222242222242424
Indoor Unit · Net Weight · Decorative Panel kg5.55.55.55.55.55.55.55.55.55.55.5
Indoor Unit · Certified Operating Range CWB14 to 2514 to 2514 to 2514 to 2514 to 2514 to 2514 to 2514 to 2514 to 2514 to 2514 to 25
Outdoor Unit · Color Ivory WhiteIvory WhiteIvory WhiteIvory WhiteIvory WhiteIvory WhiteIvory WhiteIvory WhiteIvory WhiteIvory WhiteIvory White
Outdoor Unit · Coil · Type Micro channelMicro channelMicro channelMicro channelMicro channelMicro channelMicro channelMicro channelMicro channelMicro channelMicro channel
Outdoor Unit · Compressor · Type Hermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing typeHermetically sealed swing type
Outdoor Unit · Compressor · Motor Output KW1.201.201.201.301.601.601.601.601.602.402.40
Outdoor Unit · Refrigerant (R32) kg0.7 (Charged for 10m)0.7 (Charged for 10m)0.7 (Charged for 10m)0.8 (Charged for 10m)1.0 (Charged for 15m)1.0 (Charged for 15m)1.0 (Charged for 10m)1.0 (Charged for 10m)1.0 (Charged for 10m)1.35 (Charged for 15m)1.35 (Charged for 15m)
Outdoor Unit · Sound Pressure Level · Cooling Db(A)4849495051525051525456
Outdoor Unit · Dimensions (HxWxD) mm595 x 845 x 300595 x 845 x 300595 x 845 x 300595 x 845 x 300695 x 930 x 350695 x 930 x 350695 x 930 x 350695 x 930 x 350695 x 930 x 350990 x 940 x 320990 x 940 x 320
Outdoor Unit · Net Weight kg3434343744444646466262
Outdoor Unit · Certified Operating Range *CDB21 to 4621 to 4621 to 4621 to 4621 to 4621 to 4621 to 4621 to 4621 to 4621 to 4621 to 46
Pipe Connection · Liquid (Flare) mmΦ6.4Φ6.4Φ6.4Φ9.5Φ9.5Φ9.5Φ9.5Φ9.5Φ9.5Φ9.5Φ9.5
Pipe Connection · Gas (Flare) mmΦ12.7Φ12.7Φ12.7Φ15.9Φ15.9Φ15.9Φ15.9Φ15.9Φ15.9Φ15.9Φ15.9
Pipe Connection · Drain · Indoor Unit mmVP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)VP20 (I.D.Φ20 x O.D. Φ26)
Pipe Connection · Drain · Outdoor Unit mmΦ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 18.0 (Hole)Φ 26.0 (Hole)Φ 26.0 (Hole)
Max. Pipe Length Between Units m30 (Equivalent length 40)30 (Equivalent length 40)30 (Equivalent length 40)30 (Equivalent length 40)50 (Equivalent length 70)50 (Equivalent length 70)50 (Equivalent length 70)50 (Equivalent length 70)50 (Equivalent length 70)50 (Equivalent length 70)50 (Equivalent length 70)
Max. Installation Height Difference m5050505030303030303030
Heat Insulation Both liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas pipingBoth liquid and gas piping

Related Products

Premium Aesthetics
SkyAir Duct Connection Low Static Pressure - Width Compact (FDBF)
Comfortable AirflowQuiet ModeRefrigerant R32

SkyAir Duct Connection Low Static Pressure - Width Compact (FDBF)

Hidden Concealed Duct

Capacity
2 – 6 PK
Power
1.500W – 5.300W

Blends perfectly with interior design, with no visible AC unit on the wall or ceiling.

Quick Cool
SkyAir Ceiling Cassette 3x3 (FCC)
Quick Cool

SkyAir Ceiling Cassette 3x3 (FCC)

Ceiling Cassette 3x3

3x3 feet ceiling Cassette AC with fast cooling and easy maintenance.

Business & Café Standard
SkyAir KIRIU Surround Cassette (FCFG)
Aesthetic DesignSurround AirflowSmart & Healthly

SkyAir KIRIU Surround Cassette (FCFG)

High-End Commercial & Business

Capacity
2 – 6 PK
Power
1.400W – 5.200W

The top choice for modern restaurants, offices, showrooms, and cafes, spreading cool air evenly to every corner.

Floor Standing
SkyAir Floor Standing (FVC)
Floor Standing

SkyAir Floor Standing (FVC)

Floor Standing

High-capacity floor standing AC unit for instant cooling in multipurpose halls and restaurants.

Need help choosing?